화학공학소재연구정보센터
IEEE Transactions on Energy Conversion, Vol.17, No.4, 537-542, 2002
Grid-friendly connecting of constant-speed wind turbines using external resistors
In this paper, an alternative method of connecting fixed-speed wind turbines, with active pitch mechanisms or variable-slip generators, is proposed and evaluated. Instead of using the conventional soft starter, external resistors are used. The method was evaluated via laboratory tests on a 15-kW machine and theoretically on a 1-MW wind turbine. The proposed method causes smaller grid power quality impact, especially on inductive grids, compared with soft starters. This means that it will be possible to install. constant-speed wind. turbines to weaker grids using this method.