화학공학소재연구정보센터
IEEE Transactions on Energy Conversion, Vol.22, No.2, 544-545, 2007
Control system for unbalanced operation of stand-alone doubly fed induction generators
In this letter, a novel control system for the operation of a doubly fed induction generator (DFIG), feeding an unbalanced three-phase load is presented. The load unbalance is compensated using the front-end converter. The control system is based on two revolving axes, rotating at Lo,, which are used to control the positive and negative sequence currents supplied by the front-end converter. Experimental results obtained from a 2-kW experimental prototype are presented and discussed in this letter.