Applied Energy, Vol.102, 571-581, 2013
Research on frost formation in air source heat pump at cold-moist conditions in central-south China
A dynamic evaporator model of air source heat pump (ASHP), considering the ratio of the latent heat to sensible heat of wet air, is presented to analyze the performance of ASHP under frosting. The performance parameters, such as the heating capacity, COP and the outlet temperature of compressor, are simulated with CYCLEPAD. Then a semi-empirical correlation that predicts frost accumulation on the air-side of fin-tube heat exchanger is developed with dimensionless analysis and also modified by a test conducted under cold-moist conditions in winter. In addition, eight influence factors are considered involving the ambient conditions and structures of heat exchanger, whose effects are analyzed as well. Among them, the equivalent diameter of air flow cross-section in fin-tube d(eq) is especially proposed. Lastly, the relationships between the ratio, the performance parameters and the frost accumulation are discussed in this paper, followed by an evaluation of an optimal defrosting time interval to improve the ASHP's energy efficiency and operational reliability at cold-moist conditions in central-south China. (c) 2012 Elsevier Ltd. All rights reserved.
Keywords:Cold-moist;Frost formation/accumulation;Ratio of the latent heat to sensible heat;Dimensionless analysis;Defrosting