Energy and Buildings, Vol.51, 157-164, 2012
Measured air tightness performance of residential buildings in North China and its influence on district space heating energy use
There is little known about air tightness performance of residential buildings in north China and its effect on district heating. Air tightness performance of two buildings in the cold zone of China, namely Hui'an building and Ruiguang building was measured by blower door method. Hui'an building has the average air change rate of 0.24 h(-1), and Ruiguang building has the value of 0.98 h(-1). The families located at the ends of the building have the worse air tightness performance than the families in the middle, while the performance of the family on the top floor is worse than those on the middle floor. Comparing with the foreign studies, the performance of Hui'an building is comparable with the similar buildings in Lithuania, UK, Russia and USA. but Ruiguang building has the worst performance among all these studies. Foreign standards have higher requirement, where the performance of Hui'an building can only meet the Netherlands' standard, and falls behind the standards of Finland, Belgium, Denmark. Canada, USA and UK, and Ruiguang building cannot meet any of these standards. Simulation shows the total energy use of district heating is reduced by 12.6% when ACH of Ruiguang building is reduced from 0.98 h(-1) to 0.5 h(-1). (C) 2012 Elsevier B.V. All rights reserved.