화학공학소재연구정보센터
Energy Conversion and Management, Vol.70, 230-238, 2013
Energy consumption optimization of a continuous ice cream process
This work investigates potential energy saves in an ice cream freezer by using a variable speed compressor and optimization's methodology for operating conditions during the process. Two configurations to control the refrigeration capacity were analyzed, the first one, modifies the pressure through the pilot control valve (conventional refrigeration system) and the second one with a variable speed compressor, both with a float expansion valve. Variable speed compressor configuration has showed the highest coefficient of performance and around of 30% less of energy consumption than the conventional one. The optimization of operating conditions in order to minimize the energy consumption is also presented. It was calculated only in France, for all ice cream and sorbet production, it is possible to save energy between 11 and 14 MWh per year by optimizing the operation of the refrigeration system through a variable speed compressor configuration. (C) 2013 Elsevier Ltd. All rights reserved.