Energy Conversion and Management, Vol.77, 755-762, 2014
Charging and discharging characteristics of cool thermal energy storage system with horizontal pipes using water as phase change material
An experimental investigation of ice formation on cold vertical banks of horizontal tubes subjected to falling-film- jet mode- is conducted. In the charging process, a set of internally cooled vertical banks of horizontal tubes of brine is subjected to a falling film of water. The formed ice is periodically observed, photographed and measured in falling-film jet mode at specific internal coolant (ethylene-glycol solution) flow rates and temperatures. In the discharge process, the same solution is heated and used internally to release ice. Different thicknesses of the released ice are observed and measured. The maximum quantity of released ice is obtained and the optimum ice formation is determined. The results indicate that the ice formation and the solid ice released are controlled by the thermal resistance of the ice, time and pitch between tubes. The maximum gained ice has a thickness that is approximately equal to half of the tube spacing between the tubes utilized, which is formed in approximately 45 min and released in 12.5 min. The variation in heating solution temperature has a slight effect on the gained ice and discharging time. (C) 2013 Elsevier Ltd. All rights reserved.