Solar Energy, Vol.76, No.1-3, 175-180, 2004
Performance of the Sacramento demonstration ICPC collector and double effect chiller
In 1998 two new technologies were demonstrated for the first time in a commercial building: (1) a new integrated CPC reflector evacuated solar collector (ICPC) and (2) the solar operation of a double effect absorption (2E) chiller. The 106.5 m(2) ICPC collector array consisted of 336 evacuated tubes. A commercial 2E gas-fired absorption chiller was modified to operate with 150 degreesC hot water from the solar collector array. Daily collection efficiencies of nearly 50% and instantaneous collection efficiencies of about 60% were achieved throughout the first two years of operation. Daily chiller COPs of about 1.1 were also achieved. (C) 2003 Elsevier Ltd. All rights reserved.