화학공학소재연구정보센터
Energy Conversion and Management, Vol.87, 530-538, 2014
Experimental study on the thermal performance of mechanical cooling tower with rotational splash type packing
This paper deals with an experimental investigation of thermal performance of a forced draft counter flow wet cooling tower filled with a rotational splash type packing. Tower's parameters are compared when the packing has been rotated and when it does not rotate (like common existing towers). However, no references regarding the effect of the rotational packing on the cooling tower performance have been found in the reviewed bibliography. The packing has 0.85 m(2) area and consists of six horizontal wooden slats fixed on a threaded metallic shaft. This investigation is carried out for three inlet air temperatures 27 degrees C, 34 degrees C and 41 degrees C while water temperature is kept constant at 45 degrees C. The ranges of packing velocities are between 0 to 17 RPM and also several ranges of water to air flow rate ratio are experimented: 0.4