Energy and Buildings, Vol.93, 259-268, 2015
Numerical investigation for thermal performance of exterior walls of residential buildings with moisture transfer in hot summer and cold winter zone of China
The building envelopes are exposed to the hot-humid climate with high humidity in hot summer and cold winter zone (HSCW) of China. The moisture transfer may severely influence the conduction loads through exterior walls. In this paper, a coupled heat and moisture transfer model is developed and validated to investigate the thermal performance of exterior walls. The conduction loads through a typical exterior wall are used to evaluate the effect of moisture transfer on the thermal performance of exterior walls in HSCW zone of China. The results show that the peak cooling and heating loads are overestimated by 2.1-3.9% and 4.2-10.1%, respectively, when ignoring moisture transfer. In cooling season, the sum of the latent load accounts for 14.3-52.2% of the sum of the total load and the yearly latent load accounts for 4.9-6.1% of the yearly total load when considering moisture transfer. The total cooling, heating and the yearly load are underestimated by 9.9-34.4%, 1.7-4.0%, and 5.2-6.8%, respectively, when ignoring moisture transfer. The results indicate that ignoring moisture transfer causes significant discrepancy in predicting the conduction loads. A detailed model considering moisture transfer in building envelope is essential to accurately evaluate the building energy performance in HSCW zone of China. (C) 2015 Elsevier B.V. All rights reserved.
Keywords:Coupled heat and moisture transfer;Thermal performance;Conduction load;Exterior wall;Hot summer and cold winter zone