화학공학소재연구정보센터
International Journal of Hydrogen Energy, Vol.43, No.17, 8569-8577, 2018
Effect of igniter type and number of igniters on vented deflagrations for near lean flammability limit hydrogen-air mixtures in a large scale rectangular volume
This paper examines the effect of igniter type (glow plug vs. spark igniter) and number of igniters on the dynamics of vented combustion under both initially quiescent and fan induced turbulent conditions. These experiments are a subset of many series of tests performed in a 120 m(3) large scale vented combustion test facility at the Canadian Nuclear Laboratories using near lean flammability hydrogen-air mixtures (8-12% H-2). One of the objectives of these studies was to have a better understanding of the effectiveness of deliberate ignition for mitigation of hydrogen during a postulated accident and to provide data for code validation. The test results of the current study show that the two types of ignition sources have no significant influence on the maximum combustion overpressure except that the initial burning rate is slightly faster using the spark igniter. Under either the quiescent or turbulent conditions, the maximum combustion overpressure always increases with an increase in the number of igniters, but under the current experimental conditions, the turbulent combustion overpressure with one igniter is always higher than quiescent combustion with multiple igniters. Crown Copyright (C) 2018 Published by Elsevier Ltd on behalf of Hydrogen Energy Publications LLC. All rights reserved.