Journal of the Institute of Energy, Vol.67, No.472, 109-112, 1994
A COMPARATIVE-STUDY OF VAPOR-COMPRESSION REFRIGERATION WORKING FLUIDS, IN THE WAKE OF THE MONTREAL PROTOCOL
A comparative study has been carried out of R-12, 22, 125, 134a, 152a, 218, 245, 500, 502, 507 and 717 as working fluids in a vapour-compression refrigeration system. Two performance parameters were defined, which are expressed in reduced quantities for a corresponding-states comparison of these refrigerants in the temperature range -20 to 50-degrees-C. One is based on the product of temperature drop to pressure penalty ratio and the available volumetric heat of vaporisation at the evaporator; the other considers the effect of isentropic compression in the ideal gas state. It was shown that R-125, 507 and 218 could be better alternatives to R-12 than R-134a. Among these, R-218 has a lower maximum cycle pressure.