Solar Energy, Vol.62, No.2, 79-84, 1998
Performance of a second generation solar cooling unit
This paper describes the performance of a 1.5 ton solar-operated absorption refrigeration unit operating with a 14 m(2) flat-plate solar collector system and containing five heat exchangers: the generator, the absorber, the condenser, the solution heat exchanger tall of these being of shell-and-tube type) and finally the evaporator, which is of the fin-and-tube type. One circulation primp is used for solution flow and another for the hot water flow. The condenser and the absorber are both cooled by city mains water. This particular unit, called the second generation unit, is compared with as earlier, first-generation unit (FGU), i.e. a low-cost, locally manufactured unit of 0.5 ton capacity. The results are based on the observed operation of the unit during hours of sufficient solar irradiance in April and May, the beginning of the air-conditioning season in Jordan. The variation of both the generator and evaporator temperatures during the test period are reported. Also reported is the performance of the unit as measured by the actual and theoretical (ideal) coefficients of performance, both of these being functions of the temperatures and solar irradiance. The maximum values obtained for both actual and theoretical coefficients of performance were 0.85 and 2.7, respectively. These values are within the range of values published in literature, and higher than those obtained by the FGU.