International Journal of Heat and Mass Transfer, Vol.48, No.14, 2970-2985, 2005
Investigation of flow boiling in horizontal tubes: Part II -Development of a new heat transfer model for stratified-wavy, dryout and mist flow regimes
The new version of the flow pattern map presented in Part I of this paper has been used to modify the dry angle in the heat transfer model of Kattan-Thome-Favrat [J. Heat Transfer, 120 (1) (1998) 156]. This significantly improves the heat transfer prediction in stratified-wavy flow. Moreover, a new heat transfer prediction method has been developed for the dryout and mist flow regimes, which extends the applicability of the heat transfer model to these flow regimes. An extensive flow boiling heat transfer database has been acquired for R-22 and R-410A to develop and validate the new heat transfer prediction methods. The new model also shows good agreement with the independent heat transfer data of Lallemand et al. [M. Lallemand, C. Branescu, P. Haberschill, Local heat transfer coefficients during boiling of R-22 and R-407C in horizontal smooth and microfin tubes, Int. J. Refrigeration, 24 (2001) 57-72]. (c) 2005 Elsevier Ltd. All rights reserved.