화학공학소재연구정보센터
International Journal of Heat and Mass Transfer, Vol.48, No.19-20, 4282-4286, 2005
Performance of the two-phase ejector expansion refrigeration cycle
This paper is a continuation of the authors' previous work. The paper presents new experimental data of the system performance of the two-phase ejector refrigeration cycle (TPERC). The TPERC uses a two-phase ejector as an expansion device while the conventional refrigeration cycle (CRC) uses an expansion valve. The TPERC enables the evaporator to be flooded with refrigerant, resulting in a higher refrigerant-side heat transfer coefficient. The experimental study shows that the TPERC gives a higher cooling capacity and a higher coefficient of performance. Moreover, the pressure ratio and the discharge temperature of the compressor of the TPERC are lower than those of the CRC. (c) 2005 Elsevier Ltd. All rights reserved.