Energy Conversion and Management, Vol.47, No.5, 529-544, 2006
Experimental analysis of R22 and R407c flow through electronic expansion valve
The objective of this study is to present test results and to develop a dimensionless correlation on the basis of experimental data to predict the mass flow rate of R22 and its alternative refrigerant R407c through an electronic expansion valve (EEV). The mass flow rate was measured at a series of condensing temperatures, evaporating temperatures and degrees of subcooling at the EEV inlet with five opening setting degrees of the EEV. The experimental results were analyzed, and it was found that the operation condition, flow area and the thermophysical properties of the refrigerant would affect the mass flow rate through the EEV. A new correlation based on the Buckingham pi theorem was developed to predict the mass flow rate of refrigerants through the EEV. The relative deviations of the predicted value by using this correlation are from -10.74% to 9.26% for R22 and from -14.20% to 22.10% for R407c. The average deviations and standard deviations are -0.79% and 5.02% for R22 and 0.67% and 8.08% for R407c, respectively. The relative deviation was analyzed in terms of the operation condition and flow area of the EEV. This correlation can be used to predict the mass flow rate through EEVs whose largest flow area is less than 2.544 mm(2) (c) 2005 Elsevier Ltd. All rights reserved.