Energy and Buildings, Vol.38, No.5, 447-453, 2006
Performance analysis on a hybrid air-conditioning system of a green building
This paper presents the performance analysis on a hybrid air-conditioning system according to the hybrid building energy system of the green building demonstration project in Shanghai, in which a 150 m(2) solar collector is used to power two 10 kW adsorption chillers, a vapor compression heat pump is used to cool air in the evaporating end while the condensing heating at about 80 degrees C is fully used to regenerate a liquid desiccant dehumidification system. In the hybrid system, the sensible cooling to the air is treated mainly by solar adsorption cooling and vapor compression cooling, whereas the latent heat is treated by the liquid desiccant dehumidification system with regeneration from the condensing heat of the heat pump. The results show that the performance of this system is 44.5% higher than conventional vapor compression system at a latent load of 30% and this improving can be achieved by 73.8% at a 42% latent load. The optimal ratio of adsorption refrigerating power to total cooling load for this kind of hybrid systems is also studied in this paper. (c) 2005 Elsevier B.V. All rights reserved.
Keywords:liquid desiccant;hybrid air-conditioning;adsorption refrigeration;solar energy;performance analysis