화학공학소재연구정보센터
International Journal of Energy Research, Vol.27, No.3, 203-214, 2003
Effect of magnetic field on the performance of new refrigerant mixtures
Performance test results of new alternative refrigerant mixtures such as R-410A, R-507, R-407C, and R-404A under various conditions of magnetic field are discussed, analysed and presented. The test results were obtained using an air-source heat pump set-up with enhanced surface tubing under various magnetic field conditions. Performance tests were conducted according to the ARI/ASHRAE Standards. The test results demonstrated that as magnetic field force increases, compressor head pressure and discharge temperature slightly increase as well as less liquid refrigerant is boiling in the compressor shell. This has a positive effect in protecting the compressor. The effect of magnetic field on mixture behaviour varies from one mixture to another depending upon the mixture's composition and its boiling point. Furthermore, the use of magnetic field appears to have a positive influence on the system COP as well as thermal capacities of condenser and evaporator. Copyright (C) 2002 John Wiley Sons, Ltd.