Energy and Buildings, Vol.42, No.1, 123-135, 2010
Air intrusion and its impact on energy performance of roofing assemblies
Air intrusion through roof assembly is a concern for wind uplift resistance and life-cycle performance of roofs. Airflow control is usually achieved by the installation of an air barrier/retarder in the roofing assembly. Even though the concept of air barrier/retarder and air barrier systems has been around for decades, it is still considered a new notion to the roofing industry. Currently, there are no widely accepted standard specifications or test methods to determine air intrusion through roofs or roof assemblies. An experimental procedure has been under development at the National Research Council of Canada to quantify the air intrusion of roof assemblies. As part of this investigation, five roofing assembly configurations were quantified for air intrusion. Relative performance of the air retarding effect of the five assemblies indicated that assemblies with air barrier/retarder had lower air intrusion rates than without. Measured air intrusion rates are compared with the existing codes of practice and standards. This comparison clearly demonstrates the significance of air intrusion into the roofing assembly and the necessity of a standardized air intrusion test method for the roofing industry. With the measured data, attempts were made to perform thermal load calculations using a simplified procedure, and through two case studies the impact of air intrusion through roofing assemblies on energy performance was estimated. Crown Copyright (C) 2009 Published by Elsevier B.V. All rights reserved.