Energy Conversion and Management, Vol.50, No.6, 1570-1577, 2009
Delineation of frost characteristics on cold walls by using a new formula for psychrometrics demarcation boundary
In this study, a direct formula that predicts either the frost formation on cold walls is correspondence to psychrometric-subsaturated or supersaturated regions is presented. The developed formula uses the data of the entering air dry-bulb temperature and absolute humidity, and the absolute humidity of the air at saturation corresponding to the coil surface temperature. Cases studies of demarcation criteria for frost formation on evaporator coil using experimental measured data, and on walls of cold storage freezer using measured data from literature are used to validate the formula and it is found that results are completely matches to the graphic plot of the data on the psychrometric chart. In case of cold storage freezers, the result clearly shows that a greater demarcation criteria value indicates frost formation under sever condition that is characterized as snow-like with low density and thermal conductivity. (C) 2009 Elsevier Ltd. All rights reserved.