Energy and Buildings, Vol.42, No.11, 2151-2158, 2010
Experimental study on airflow fluctuation characteristic of an underfloor air supply terminal unit
In order to investigate dynamic characteristic of underfloor air supply terminal unit, an IFV900A hot-wire anemometer was used to measure the corresponding velocity field. Turbulence intensity and power spectrum density exponent of air velocity signal were analyzed. The result showed that the outlet velocity distribution of underfloor air supply terminal unit was uniform. With increment of height, the velocity distribution trends to be uniform. Two velocity attenuation regions appear during airflow development. Turbulence intensity changes obviously with height. It is lower than that of mechanical wind. Turbulence intensity goes up with the increment of jetting distance. Power spectrum density exponent trends to the value of natural wind with increase of jetting distance and decrease of wind velocity. The exponent value approaches to the value of typical natural wind for the air velocity is 0.5 m/s under high supply air rate. With airflow diffusion, the fluctuation characteristic of airflow varies obviously with the jetting direction. The fluctuation characteristic of airflow changes to that of natural wind with the increase of height which can improve comfort of indoor environment. (C) 2010 Elsevier B.V. All rights reserved.
Keywords:Underfloor air supply terminal unit;Turbulence intensity;Power spectrum density;Airflow fluctuation characteristic