Energy Conversion and Management, Vol.52, No.1, 770-780, 2011
Experimental study of hydronic panels system and its environment
An experimental analysis of hydronic cooling or heating ceiling panels coupled to the building is present in this investigation as a part of the commissioning study of this system. Two test chambers are adapted in a way to reproduce the interaction of the system to the building (windows, internal thermal loads distribution, building structure and ventilation). A series of experimental tests were performed in which the main objective is to observe the influence of parameters such as the water mass flow rate, supply water temperature, thermal load distribution, window and ventilation system effects on the hydronic ceiling capacity and comfort conditions. Test results show that the influence of asymmetric surfaces temperatures inside the room, especially the window effect is not negligible. Then, it is clear that the cooling hydronic ceiling must be evaluated coupled to the building systems and structure. (C) 2010 Elsevier Ltd. All rights reserved.