화학공학소재연구정보센터
International Journal of Energy Research, Vol.22, No.7, 603-614, 1998
Thermodynamic studies on HFC134a-DMA double effect and cascaded absorption refrigeration systems
The double-effect vapour absorption refrigeration system working with HFCl34a as refrigerant and dimethyl acetamide as absorbent is analysed. Cooling coefficients of performance in the range of 0.5-0.9 could be obtained depending on the operating conditions. However, sub-zero temperatures are difficult to obtain at typical heat source and heat rejection temperatures. Hence, cascaded systems are suggested for achieving low temperatures.