화학공학소재연구정보센터
Energy and Buildings, Vol.42, No.12, 2338-2352, 2010
Floor heating and cooling combined with displacement ventilation: Possibilities and limitations
Design guidelines envisage that floor heating can be used together with displacement ventilation (DV), provided that the supply air is not overly heated before it can reach heat and contaminant sources. If this is not controlled a mixing flow pattern could occur in the room. The use of floor cooling with DV is also considered possible, although draught risk at ankle level and vertical air temperature differences must be controlled carefully, because they could increase. Few studies on these topics were found in the literature. An indoor environmental chamber was set up to obtain measurements aimed at analysing the possibilities and limitations of combining floor heating/cooling with DV. Air temperature profiles, air velocity profiles, surface temperatures and ventilation effectiveness were measured under different environmental conditions that may occur in practice. These values were compared to equivalent temperature measurements obtained using a thermal manikin. The measurements show that floor heating can be used with DV, obtaining high ventilation effectiveness values. A correlation between the floor heating capacity and the air temperature profile in the room was found. Measurements showed that floor cooling does not increase draught risk at ankle level, although it does increase vertical air temperature differences. (C) 2010 Elsevier B.V. All rights reserved.