Energy and Buildings, Vol.42, No.12, 2353-2359, 2010
Analysis on the impact of mean radiant temperature for the thermal comfort of underfloor air distribution systems
Despite the potentially significant advantages of underfloor air distribution (UFAD) systems, the shortcomings in fundamental understanding have impeded the use of UFAD systems. A study has been carried out on the thermal stratification which is crucial to system design, energy efficient operation and comfort performance of UFAD systems with an aim of examining impact of mean radiant temperature (MRT) on thermal comfort. Clear elucidation of the benefit of UFAD systems has been shown by comparing it to the traditional overhead air distribution systems. Keeping the same level of comfortable environment in the occupied zone. UFAD systems require much higher temperature of supply air, which represents significant energy savings. The benefit of UFAD systems is more pronounced at the condition of high ceiling height building. Considerable discrepancies in thermal comfort are found on the assumption that air temperature rather than MRT is used for the evaluation of PMV. However, more rigorous analysis including the full radiation simulation does not show any significant difference in PMV distribution. The result of the full radiation simulations requires much longer simulation time but gives similar air temperature distribution and only slightly higher averaged temperature than present approaches. (C) 2010 Elsevier B.V. All rights reserved.
Keywords:Underfloor air distribution;Mean radiant temperature;PMV (predicted mean vote);Thermal comfort